PrecauLarge.PMD An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with.
ANN-80 80-Character Serial LCD Annunciator Annunciators DF-52417:D. B-90 General The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, andarm Silenced conditions. The ANN-80 Al. – Optional Remote LCD Annunciator N-ANN-80. Nection for a serial or parallel printer. N-ANN-I/O: Driver module. Provides connections to a user-supplied graphic annunciator. ACCESSORIES DP-51050: Optional dress panel. Restricts access to the sys-tem wiring while allowing access to the membrane switch. Conventional Fire Alarm Control Panels dn-60185:c 60185cov.jpg General The SFP-5UD is a five-zone FACP (Fire Alarm Control Panel) and the SFP-10UD(E) is a ten-zone FACP. These control pan-els provide reliable fire signaling protection for small to medium-sized commercial, industrial,. DN-60955:A. 3/6/2018 — Page 1 of 4 NFW-50X Intelligent Addressable FACP with Communicator General The FireWarden-50X (NFW-50X) is the latest intelligent address- able fire alarm control panel (FACP) within the FireWarden Series. The NFW-50X comes with a pre-installed communicator and sup.
N-ann-80, Character lcd serial annunciator, General
Advertising
dn-7114:c • 5/22/09 — Page 1 of 2
N-ANN-80
80-Character LCD
Serial Annunciator
Annunciators
dn-7114:c • A1-65
71
14c
ov
.jpg
General
The N-ANN-80 annunciator is a compact, backlit, 80-character
LCD fire annunciator that mimics the Fire Alarm Control Panel
(FACP) display. It provides system status indicators for AC
Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi-
tions. The N-ANN-80 and the FACP communicate over a two-
wire serial interface employing the ANN-BUS communication
format. Connected devices are powered, via two additional
wires, by either the host FACP or a remote UL-listed, filtered
power supply. N-ANN-80 is black; for white order N-ANN-80-W.
The N-ANN-80 displays English-language text of system point
information including device type, zone, independent point
alarm, trouble or supervisory status, as well as any custom
alpha labels programmed into the control panel. It includes con-
trol switches for remote control of critical system functions. (A
keyswitch prevents unauthorized operation of the control
switches.)
Up to eight N-ANN-80s may be connected to the ANN-BUS of
each FACP. Minimal programming is required, which saves time
during system commissioning. The N-ANN-80 is compatible
with NOTIFIER FACPs with an ANN-BUS, such as the NFW-50.
Features
• Listed to UL Standard 864, 9th Edition.
• Backlit 80-character LCD display (20 characters x 4 lines). • Mimics all display information from the host panel. • Control switches for System Acknowledge, Signal Silence,
Drill, and Reset.
• Control switches can be independently enabled or disabled
at the FACP.
Coolpad Phones in China mainly acquires youth, as the device combines the rich content of the programs and the modern stylish design. However, there is absolutely a model for all users, as strict for work or a business meeting, and bright for a holiday or a friendly evening and a variety of sizes to help you choose the phone, based on the needs of the tempo and rhythm of life of the user. Coolpad Note 3 Lite Full phone specifications, specs, Manual User Guide - My Store, Amazon. Coolpad note 3 lite update. Coolpad Note 3 User Manual Download. Coolpad Note 3 Release in October 2015 comes with Android 5.1 (Lollipop), MediaTek chipset, 3 GB, Display size 5.5 Inch, 720 x 1280 pixels (HD) Screen Resolution, 13 MP Primary Camera, Li-Ion 3000 mAh Battery, weight 168g release price USD 123, EUR 108, INR 8500. Coolpad Note 3 Lite manual user guide is a pdf file to discuss ways manuals for the Coolpad Note 3 Lite.In this document are contains instructions and explanations on everything from setting up the device for the first time for users who still didn’t understand about basic function of the phone.
• Keyswitch enables/disables control switches and mechani-
cally locks annunciator enclosure
• Keyswitch can be enabled or disabled at the FACP.
• Enclosure supervised for tamper. • System status LEDs for AC Power, Alarm, Trouble, Supervi-
sory, and Alarm Silence.
• Local sounder can be enabled or disabled at the FACP.
• N-ANN-80 connects to the ANN-BUS terminal on the FACP
and requires minimal panel programming.
• Displays device type identifiers, individual point alarm, trou-
ble, supervisory, zone, and custom alpha labels.
• Time-and date display field.
• Surface mount directly to wall or to single, double, or 4'
square electrical box.
• Semi-flush mount to single, double, or 4' square electrical
box. Use ANN-SB80KIT for angled view mounting.
• Can be remotely located up to 6,000 feet (1,800 m) from the
panel.
• Backlight turns off during AC loss to conserve battery power
but will turn back on if an alarm condition occurs.
• May be powered by 24 VDC from the host FACP or by remote
power supply (requires 24 VDC).
• Up to eight N-ANN-80s can be connected on the ANN-BUS.
Controls and Indicators
• AC Power
• Alarm
• Trouble
• Supervisory • Alarm Silenced
Specifications
•
Operating voltage range: 18 VDC to 28 VDC.
•
Current consumption @ 24 VDC nominal (filtered and non-
resettable): 40 mA maximum.
•
Ambient temperature: 32°F to 120°F (0°C to 49°C).
•
Relative humidity: 93% ± 2% RH (noncondensing) at 32°C
± 2°C (90°F ± 3°F).
• 5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375”
(3.49 cm.) deep.
• For use indoors in a dry location.
• All connections are power-limited and supervised.
Agency Listings and Approvals
The listings and approvals below apply to the N-ANN-80. In
some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory
for latest listing status.
•
UL: S635
• FM approved
•
CSFM: 7120-0028:240
•
MEA: 442-06-E Vol. 2
Lcd 80 Annunciator
The ANN-BUS
POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY
The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS devices exceeds the
ANN-BUS power requirements. See the FACP manual for more
information.
Advertising
Popular Brands
Popular manuals
Advertising
38
50 Pt Addr Panel
PS-Tools
08/2010
Configuring Fire Panels
ANN-80 Options
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics
the display on the control panel annunciates device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employing the ANN-Bus communication format.
To configure the ANN-80 module
1.
Select Yes to enable the Lock Enable option which allows you to unlock the ANN-80 keypad
with its own key. If you select No, the keylock is ignored and the ANN-80 keypad buttons are always enabled.
2.
Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80 module. The piezo sounder is disabled when you select No.
3.
Select Yes in ACK Enable to enable the normal function of the ACK Button on any installed
ANN-80 annunciator. This option is ignored if you select No.
4.
Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80
annunciator.
5.
Select Yes in Reset Enable to enable the Reset Button on any installed ANN-80 annunciator.
6.
Select Yes in DrillEnable to enable the Drill Button on any installed ANN-80 annunciator(see
).
Note
You must enable the canadian option to configure the following ANN-80C modules.
To configure the ANN-80C module
1.
Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80C module. The piezo sounder is disabled when you select No.
2.
Select Yes in Step Enable to enable the normal function of the Step Button on any installed
ANN-80C annunciator. This option is ignored if you select No.
3.
Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80C
annunciator.
4.
Select Yes in LampTest Enable to enable the lamptest Button on any installed ANN-80C
annunciator.
5.
Select Yes in Sounder TestEnable to enable the sounder Button on any installed ANN-80C
annunciator.